TEST BUILD — an unstable work in progress, not the released simulator. Things here are half-finished on purpose. The stable version is at reactordynamics.com.

PWR Operator Manual · Open the simulator

07 — Abnormal and Emergency Operating Procedures

Document: PWR-EOP-01
Title: Failure Response — PWR Trainer
Revision: 24


1.0 Purpose

Provide symptoms, automatic response, immediate operator actions, recovery, and acceptance criteria for every modeled PWR failure. Inject from Tools → Failures in Free Play, or encounter via missions.

Typical applicability: failures are injected in Mode 1, At Power (at power). Successful trip recovery leaves the plant in Mode 3, Hot Standby (hot, subcritical). See 05_MODE_TRANSITIONS.md PWR-T06.

2.0 Failure index

IDFailure (UI display)Category
PWR-E01Loss of Main Feedwaterpower
PWR-E02RCP Tripcoolant
PWR-E03Turbine Trippower
PWR-E04Loss of Offsite Powerpower
PWR-E05Station Blackoutpower
PWR-E06Steam Generator Tube Rupture (SGTR)coolant
PWR-E07PORV Stuck Open (SBLOCA)coolant
PWR-E08PORV Indicator Stuck Closedinstrument
PWR-E09Small-break LOCA (cold leg)coolant
PWR-E10Loss of Condenser Vacuumpower
PWR-E11Degraded HPIsafety_system
PWR-E12Auxiliary Feedwater Failuresafety_system
PWR-E13Failure to Scram (ATWS)safety_system
PWR-E14Pressurizer Spray Stuck Opencoolant
PWR-E15Pressurizer Heaters Failedcoolant
PWR-E16SG Overfeed / Overcoolingpower
PWR-E17Continuous Rod Withdrawalreactivity
PWR-E18Control Rod Stuck on Scramreactivity
PWR-E19Main Steam Line Break (downstream of MSIV — isolable)power
PWR-E19uMain Steam Line Break (upstream of MSIV — not isolable)power
PWR-E20Tavg Sensor Driftinginstrument
PWR-E21Pressurizer Level Sensor Stuckinstrument
PWR-E22Pressurizer Level Sensor Failed Lowinstrument
PWR-E23Reactor Coolant Pump Seal Leakcoolant

Combined drills: E07 + E08 = TMI indicator deception (see PWR-X01).

2.1 Failure severity sliders

Most failures inject at a fixed severity; eight carry a slider (Tools → Failures). The slider is the failure's physical size — the response procedures below apply at any setting.

FailureSliderRangeDefault
SG Tube Rupture (E06)Rupture Severity0 – 100 % of full rupture40 %
Degraded HPI (E11)HPI Capacity100 → 0 % of rated50 %
Small-break LOCA, cold leg (E09)Break Size0 – 100 % — 100 % is a 3.1 in² (20 cm²) hole40 %
Continuous Rod Withdrawal (E17)Withdrawal Rate8 – 72 steps/min — the drive's own slow-to-fast band40
Rod Stuck on Scram (E18)Rod Worth Held0 – 40 % of total20 %
Main Steam Line Break, downstream (E19)Break Size0 – 100 % effective area30 %
Main Steam Line Break, upstream (E19u)Break Size0 – 100 % effective area30 %
RCP Seal Leak (E23)Leak Rate0 – 100 % of make-up capacity40 %

3.0 Generic immediate actions (any upset)

PriorityAction
1Protect the core: verify SCRAM if required; manual SCRAM if power should be down and is not
2Heat sink: SG level — feed or AFW
3Inventory & subcooling: pressure, HPI, isolate open relief path
4Load: turbine disconnected or matched
5Diagnose on diverse instruments — never one light
6Securing an engineered-safeguards actuation is a RESET, not a MANUAL selection — there is no ESF arm on this plant, and the pumps are held running until the reset permissive is satisfied (03 §17.4)

PWR-E01 — Loss of Main Feedwater

Failure

loss_of_feedwater — feed commands forced to zero / feed lost.

Symptoms

Automatic

Timing — what to expect

From a total loss of main feedwater at full power, measured: AFW auto-start at about 3 s (the feed-flow start — level is still ~65 %), SG LVL LO (30 %) at about 29 s, SG LVL LO LO and the reactor trip at about 40 s. That leaves roughly 11 s between the first warning and the trip, with AFW already feeding the whole way down.

Expect the trip. You are not going to prevent it. Even restoring feed the instant the warning comes in still trips the plant — the feed pump takes time to come back up while the generator keeps boiling. That is prototypical, not a limitation: a real loss of normal feedwater trips the reactor on low-low steam generator level, and that trip is the credited protection for the event. Use the window to confirm the diagnosis and to check that AFW is lined up and coming, not to chase the trip.

Immediate actions

StepAction
1Confirm SG level falling / feed lost
2SCRAM if not tripped
3Turbine load 0 / Disconnected
4AFW Start (verify delivery by level response)
5Verify AFW holds level without severe overcooling — the afw_level channel throttles the valves; the board's levers are STOP and AUTO
6Stabilize PZR pressure

Recovery / acceptance

Reactor shut down; SG inventory restored on AFW; core not damaged (fuel safe); subcooling restored.

If AFW also failed

See PWR-E12 — critical heat-sink challenge; minimize heat load (verify scram) and use any remaining secondary path.


PWR-E02 — RCP Trip / Loss of Flow

Failure

rcp_trip — pump stop / flow coastdown.

Symptoms

Immediate actions

StepAction
1Verify reactor trip (manual SCRAM if needed)
2Remove turbine load
3Maintain secondary heat sink (AFW/feed as available)
4Allow natural circulation for decay heat
5Monitor subcooling and inventory

Acceptance

Shutdown; cooled without fuel damage.


PWR-E03 — Turbine Trip

Failure

turbine_trip — load commands overridden to 0; reconnect blocked.

Symptoms

WARNING — a turbine trip above P-9 scrams the reactor. This plant carries **Reactor Trip on Turbine Trip** (P-9, ≥ 50 % power). Do not plan to "ride out" a turbine trip at power. What this plant rides out is a load rejection — the generator taking less load with the turbine still on line — which is a different event and does not arm P-9.

A planned offline is not a turbine trip. Taking the generator off line with the OFF selector (disconnect_grid) opens the breaker: load goes to zero, the stop valves stay open, no trip latches, and P-9 never arms. It is reversible with FOLLOW or MAN. See 03 §12.1.

Immediate actions

StepAction
1Verify 0 MWe
2Above P-9: confirm the automatic reactor trip and go to the post-trip response. Below P-9: insert rods to match the lost load, or SCRAM if pressure/Tavg is challenged
3Steam dump as needed for secondary pressure
4Control SG level (swell/shrink)
5Stabilize at Hot Shutdown or low power per drill

Acceptance

Load rejected safely; above P-9 the reactor tripped automatically and the plant is stable on the dump and AFW; below P-9 nuclear power matched or scrammed. No SG dryout or flood.

Note — high-high SG level (P-14)

A high-high SG level (≥90 %) — from overfeed or a steam-line-break level swell — trips the turbine automatically to protect it from moisture carryover, isolates main feedwater (AFW keeps feeding), and trips the reactor if power is ≥50 % (the P-9 interlock). Expect all three together. Main feed stays isolated until you restore it deliberately once level is controlled; verify AFW is carrying the heat sink in the meantime. Annunciates as SG LVL HI HI (PWR-A16b).


PWR-E04 — Loss of Offsite Power

Failure

loss_of_offsite_power — pump coast-down class effect.

Symptoms

Immediate actions

StepAction
1Verify SCRAM
2Verify heat sink (AFW preferred when main feed lost with power)
3Natural circulation monitoring
4Inventory/pressure control with available systems

Acceptance

Core covered and cooled on available systems.

Note

Distinct from full SBO (E05); still treat heat sink as priority.


PWR-E05 — Station Blackout (SBO)

Failure

station_blackout — full blackout effect as modeled.

Symptoms

Immediate actions

StepAction
1Verify reactor shutdown
2Start/verify AFW if available under blackout model
3Minimize DC/control load conceptually; act quickly
4Natural circulation / secondary heat removal focus
5Verify natural circulation is established — loop ΔT steady, subcooling positive, SG pressure stable. It needs a liquid-filled loop: if the primary voids, circulation stops and does not come back

Acceptance

Core covered and cooled on natural circulation with AFW. This is achievable — measured, an SBO holds the core with subcooling squeezing to 9 °F (5 °C) around 30 minutes and recovering thereafter.

Note

The blackout takes the CVCS and the ECCS pump with it — charging, letdown and safety injection are all Class 1E ac loads, so inventory only falls. AFW is turbine-driven and keeps running. Natural circulation moves heat to the steam generator; it does not remove it, so the secondary heat sink stays the priority.


PWR-E06 — Steam Generator Tube Rupture (SGTR)

Failure

sgtr — primary-to-secondary leak; severity = 0 – 100 % of a full double-ended tube rupture, default 40 %.

Symptoms

DECLARED DEPARTURE — the secondary does not receive the leak (design notes §8.26, ruled 2026-08-03). On a real plant a tube rupture raises level and activity in the affected generator, and that is how you identify which one. This trainer models one steam generator, so that lesson cannot exist here at all — and the leak is modelled as a primary-side mass sink with ΔP modulation, delivering neither mass nor energy to the secondary. Measured: with the leak at 0.011–0.015 frac/s and feed, AFW and steam flow all at zero, SG level held at 67.98 % constant for four minutes. **An earlier revision of this page listed "possible rising SG level" as a symptom. It does not happen; that line is withdrawn.**

Immediate actions

StepAction
1SCRAM if not automatic / as pressure falls
2Identify the leak on the PRIMARY side — inventory falling with charging saturated, level below program and still going, subcooling eroding. The steam generator will not confirm it for you (see the departure above)
3Maximize charging / ensure HPI as needed
3aSECURE high-pressure injection before you depressurize — and the criteria are a STANDING CONDITION, not a one-time check. Before you secure: subcooling in hand, heat sink established on AFW, core covered. After you secure: keep watching subcooling — on this plant it does not stay in hand. Measured, criteria genuinely met at the click (5.4 °F / 3.0 °C of margin) and injection secured anyway: subcooling reaches 0 °F (0 °C) by minute twelve and stays there, while leaving injection in holds 4.8–6.2 °F (2.7–3.4 °C) indefinitely. The margin you checked is gone twelve minutes later. Step 3b is the re-entry and it is not optional. This step is what makes step 4 work at all. Injection holds the primary up at pressure, so with it running the Pressure SP barely moves break flow: re-measured on PWR2 (2026-09-18, full stack, hot_full_power, 40 % severity — see the Note below), walking the setpoint 2235 → 1450 psi (15.41 → 10.0 MPa) with HPI still running cut break flow ≈1 %, unchanged from one minute to twenty — inventory held near 88 % and subcooling held 5.4–7.2 °F (3.0–4.0 °C), not the drift toward solid the retired engine reported. Securing injection first, then the same setpoint walk, cut break flow 42 % in one minute, easing further to 49 % by twenty (still declining, not flat) — the core argument survives, at roughly half the retired engine's reported magnitude. Same reason every real SGTR procedure carries an SI-termination step: injection and depressurization work against each other
3bRE-ENTRY — if subcooling reaches zero, RESTORE high-pressure injection. Do not ride a saturated primary to finish the depressurization. Measured on the same transient: restoring injection at the zero crossing brings subcooling back to 6.6 °F (3.7 °C) within five minutes and it holds 5.9–6.9 °F thereafter, with core inventory recovering 87.0 → 88.3 %; the same plant left alone sat at 0 °F for fifteen minutes and was still at 0.5 °F at thirty. The re-entry works — but verify it on HPI FLOW, not on the HPI ACTUATED light. HPI ACTUATED is the safety-injection SIGNAL, not a reading of delivered flow (12 §6.3): the plant fired it for you the first time, and when you restart the pumps below the actuation setpoint it stays dark while water moves. HPI FLOW reads ~0.12 of rated and subcooling starts climbing within a minute — those two are your confirmation. HPI DISCHARGE PRESSURE confirms it too — re-measured on the fixed gauge: ~1069 psi (7.37 MPa) at the same operator-restored point that used to read zero. Once margin is restored, return to step 4 and continue the depressurization
4Depressurize primary carefully toward secondary pressure to reduce break flow (heaters off, spray if available, PORV only with care)
5Isolate / control steam paths per training objective (MSIV strategy if used). Re-measured on PWR2: the MSIV DOES change the secondary pressure trend — the retired engine's "no effect" claim is WITHDRAWN. Same failure and schedule, diverging only in the MSIV command: open, secondary pressure eased to 1024 psi (7.06 MPa) by twenty minutes; shut, the ADV opens as the alternate relief path and secondary pressure instead climbs to 1060 psi (7.31 MPa) — a 36 psi (0.25 MPa) gap, identical across six instrument-noise seeds (0 psi spread — this is not noise; see the Note below). SG pressure still tracks Psat(Tavg) as designed, but Tavg itself is not independent of which steam path is open
6Maintain heat sink and subcooling

Acceptance

Break flow reduced; core covered; plant stabilized for “cooldown” narrative.


PWR-E07 — PORV Stuck Open (Small-Break LOCA)

Failure

stuck_porv_open — close_porv overridden; PORV remains open.

Symptoms

Immediate actions

StepAction
1Diagnose on subcooling, pressure, inventory — not PORV light alone
2Command PORV Close (may fail)
3PORV Block Valve → Isolate (CONFIRM?) — stops the leak
4Ensure HPI running; do not throttle for high PZR level
5SCRAM if required
6Restore pressure/inventory/subcooling

Acceptance

Block valve isolated; inventory trend stabilized; core covered; melted false.

Key teaching

This is the recovery missed at TMI. See PWR-X01.


PWR-E08 — PORV Indicator Stuck Closed

Failure

porv_indicator_stuck_closed — indicator forced closed regardless of true valve.

Symptoms

Immediate actions

StepAction
1Treat PORV light as untrusted
2Use subcooling, tailpipe temperature, pressure, inventory
3If leak signature present → isolate block valve (E07 steps)
4In Learning mode, dual Indicated/Actual may reveal the lie — practice without it in Realistic

Acceptance

Operator does not use the light as sole truth.


PWR-E09 — Small-break LOCA (cold leg)

Failure

A primary-coolant leak from the cold leg. Severity is the break size: 0 – 100 %, where 100 % is a 3.1 in² (20 cm²) hole — a small break by the industry's sizing, which is why the failure carries that name (default 40 %). At full size it still outruns make-up, trips the reactor and brings in safety injection and the accumulators.

Symptoms

Immediate actions

StepAction
1Verify SCRAM
2Verify HPI On (manual if needed) — leave on
3Confirm accumulators discharge when pressure low enough
4Secondary heat sink for residual heat if available
5Do not secure ECCS on misleading level
6Expect PZR HTRS SHED — safety injection drops the heaters off the bus. Leave them shed while you are still losing inventory: pressure control is not the problem here, and reloading them raises break flow. Reload only once the leak is isolated and you want pressure back.

Acceptance

Core cooling maximized; damage avoided if injection timely. Large breaks are severe — success = covered core / no melt when systems work.


PWR-E10 — Loss of Condenser Vacuum

Failure

loss_of_condenser_vacuum — vacuum decay.

Symptoms

Immediate actions

StepAction
1Reduce load early if vacuum falling
2Verify turbine trip when required
3Control reactor (SCRAM if heatup/pressure)
4Steam dump may be limited without vacuum — watch SG pressure
5AFW / heat sink management

Acceptance

Turbine protected; reactor stable shutdown or matched state.


PWR-E11 — Degraded HPI

Failure

degraded_hpi — reduced HPI capacity (severity slider: capacity %; lower capacity = worse).

Symptoms

Immediate actions

StepAction
1Verify HPI demand On
2Isolate break if possible (PORV block, etc.) to reduce required injection
3Depressurize only as strategy requires — match pump curve (more flow at low P)
4Maximize secondary heat removal to reduce primary boil-off
5Watch fuel status / subcooling

Acceptance

Best achievable cooling; isolate break; avoid melt if capacity allows.


PWR-E12 — Auxiliary Feedwater Failure

Failure

afw_failure — AFW delivery blocked (pumps may still indicate running).

Symptoms

Immediate actions

StepAction
1Verify main feed status; attempt main feed if failure allows
2SCRAM (minimize heat)
3Confirm AFW failure by level not rising
4Use any remaining heat sink path (steam dump / residual feed)
5Primary feed-and-bleed class thinking: HPI + PORV path only as last resort training concept

Acceptance

Core protected if any heat sink restored; recognize dual failure severity.


PWR-E13 — Failure to Scram (ATWS)

Failure

failure_to_scram — the rods fail to drop. The trip itself is not blocked: the pushbutton is accepted, the trip latches, annunciators come in and the turbine trips. It is the rod insertion that fails.

Symptoms

Immediate actions

StepAction
1Attempt manual SCRAM again (may still fail)
2Emergency boration (CVCS Borate, charging On) — max rate
3Insert rods manually if any motion possible
4Reduce turbine load carefully or trip turbine per power/heat sink strategy
5Maintain feed/AFW — ATWS + dry SG is catastrophic
6Lower power by heat-up / MTC if plant allows while borating

Acceptance

Power driven down; core cooled; eventually subcritical. Stuck-rod partial ATWS see E18.


PWR-E14 — Pressurizer Spray Stuck Open

Failure

stuck_open_spray — spray forced open.

Symptoms

Immediate actions

StepAction
1Attempt spray close / AUTO (may fail)
2Energize heaters max — if injection has actuated they are shed (PZR HTRS SHED) and will not answer until reloaded
3If pressure approaches trip/HPI, SCRAM as required
4Stop RCP only if procedure/drill requires (spray needs flow — stopping RCP reduces spray effectiveness but loses forced flow) — prefer pressure recovery without at-power RCP stop
5HPI if pressure LO-LO path

Acceptance

Pressure stabilized or plant safely tripped and controlled.


PWR-E15 — Pressurizer Heaters Failed

Failure

failed_pzr_heaters — heater power forced off.

Symptoms

Immediate actions

StepAction
1Secure spray
2Reduce cooldown / match load and power to stop pressure bleed
3Use inventory strategy carefully (insurge)
4SCRAM if subcooling threatened and unrecoverable
5HPI if pressure collapses

Acceptance

Subcooling maintained or safe shutdown on HPI/heat sink.


PWR-E16 — SG Overfeed / Overcooling

Failure

sg_overfeed — feed forced high (~120 % pump speed class).

Symptoms

Immediate actions

StepAction
1Attempt feed reduce / MANUAL take-over (may be overridden by failure)
2SCRAM if power/Tavg excursion severe
3Reduce turbine steam demand carefully if overcooling-driven power rise
4When failure cleared, restore normal feed AUTO

Acceptance

Level returned to band; primary temperature controlled; no trip if recoverable, else safe trip.


PWR-E17 — Continuous Rod Withdrawal

Failure

continuous_rod_withdrawal — a rod control unit failure holds the drive in outward motion. The slider is the speed the failed controller is demanding, and it runs across the drive's own band: 8 steps/min at the bottom to 72 steps/min at the top, 40 by default. The top of the slider is the real accident's own initiating event — *"Rod control system controller failure withdraws bank D rods at 72 steps/min"* (NRC HRTD Advanced Transients, Transients 5.22 and 5.23) — and it is also the rod speed programmer's mechanical maximum and this plant's own fast drive, which are the same number: 72 steps/min. So the top of the slider is both the fastest withdrawal this drive can produce and the rate the sourced accident states.

The rod stop will not save you here, by design. The intermediate-range high-flux rod stop inhibits the demand path; a drive fault is downstream of it. The stop asserts and the bank keeps coming — what ends it is the reactor trip a second or so later, or your scram.

Symptoms

From hot zero power at the top of the slider, measured: SUR HI annunciates at 169 s after injection, the rod stop asserts at 229 s and the intermediate-range high-flux trip follows at 230 s, peaking at 35 % power and 31 decades per minute. At the default setting the trip comes at 6.7 minutes; at the bottom of the slider the same sequence takes 33 minutes. It is a rising transient you have time to act on — that is the point of it.

Immediate actions

StepAction
1Attempt Lower (hold) to insert against the runaway
2SCRAM immediately if motion continues
3After trip, verify rods in (unless E18)
4Stabilize heat sink

Acceptance

Power terminated; scram successful or ATWS path if combined.


PWR-E18 — Control Rod Stuck on Scram

Failure

stuck_rod_on_scram — portion of rod worth held out; severity % worth held.

NOT INJECTABLE ON THIS PLANT. The lever does not exist in the shipped failure menu, so you cannot cause this one deliberately. The procedure is kept because the condition is real operator knowledge and because the reasoning — a scram that does not take power as low as it should, and what you do about it — is exactly what the boration steps below teach. Read it as reference, not as a drill you can run.

Symptoms

Immediate actions

StepAction
1Verify scram signal present
2Emergency borate
3Maintain heat sink aggressively
4Treat residual power as ATWS-lite
5Do not assume “scrammed = zero heat”

Acceptance

Power reduced by boron/feedback; core cooled; damage avoided.


PWR-E19 — Main Steam Line Break

Failure

steam_line_break — break downstream of the MSIV (turbine hall); severity break size %.
steam_line_break_upstream — break upstream of the MSIV (between generator and valve); same severity scale.

NOT INJECTABLE ON THIS PLANT — neither of them. The MSIV itself is built and works, and the automatic isolation signal is not — so the break that would exercise it has no lever in the failure menu. The procedure is kept: the location-decides-the-outcome reasoning below is the whole lesson of the event and it is true of the plant's steam path as modelled. Read it as reference, not as a drill you can run.

The location decides whether you can end it. The MSIV sits between the steam generator and the turbine. A break downstream of the valve is on the far side of it, so shutting the MSIV puts steel between the generator and the break and the blowdown stops. A break upstream is on the generator side, where no isolation this plant owns can reach it — it blows the generator down whatever you shut. A multi-loop plant answers a steam line break by isolating the faulted generator and steaming the intact ones; this plant has one generator, so against an upstream break there is nothing to fall back on. Trip, and ride the cooldown out.

Symptoms

Immediate actions

StepAction
1SCRAM
2MSIV Close (two-press). Downstream break: this terminates it — steam pressure stops falling and the bottled generator re-pressurizes to its code safeties — a staggered bank, first lift 1099 psi (7.58 MPa) and the rest at 1155 psi (7.96 MPa) (09 §3.0) (formerly stated as a single 1350 psi (9.31 MPa) lift / 9.0 reseat), and you are now in the bottled-SG condition of alarm card PWR-A23. Upstream break: it will not help — steam pressure keeps falling; do not wait on it
3Stop AFW/feed overfill into faulted path if level high
4Control pressure (spray/heaters) as primary cools
5Borate if return-to-power risk
6Stabilize intact heat sink — after a successful isolation the generator is bottled and dry-heading toward the low-level trip; feed it (AFW) and control pressure per PWR-A23

Acceptance

Break isolated (downstream) or effects mitigated (upstream); reactor shut down; core cooled without melt.

Model honesty. There is no automatic safety injection on low steam-line pressure in this plant, and none is needed — the scrammed core holds more than 9,600 pcm subcritical through a full blowdown even with the maximum stuck rod, so there is no return-to-power to borate against. Real plants carry the interlock; here it would inject into an intact primary with nothing to make up. Pressurized thermal shock — a cold, deeply subcooled primary held at full pressure — is a genuine concern this model does not represent.


PWR-E20 — Tavg Sensor Drifting

Failure

tavg_sensor_failure — instrument drift on Tavg.

Symptoms

Immediate actions

StepAction
1Place Rod control AUTO → MAN
2Control on power, Thot/Tcold, pressure, not drifted Tavg alone
3Expect protection that reads Tavg instrument to be fooled (HR1)
4Stabilize plant manually
5Clear failure when drill ends

Acceptance

No rod run from bad AUTO; plant stable on diverse indications.


PWR-E21 — Pressurizer Level Sensor Stuck

Failure

pzr_level_sensor_stuck — level instrument frozen.

Symptoms

Immediate actions

StepAction
1CVCS inventory → MANUAL
2Control inventory using pressure, subcooling, charging/letdown flows, power history
3Do not trust stuck level for HPI throttle decisions
4In Learning/overlay, compare truth if teaching — Realistic: diverse only

Acceptance

No LOCA-style HPI throttle error; inventory managed.


PWR-E22 — Pressurizer Level Sensor Failed Low

Failure

pzr_level_sensor_low — the level channel fails and reads a fixed LOW value (~20 %) regardless of true level.

Symptoms

The teaching point

The PI-8 going-solid trip (97 %) reads this same single channel — with the sensor failed low, that backstop is defeated. An overfill driven by the wrong-charging CVCS (or by an over-eager operator) can now take the pressurizer solid with no automatic protection: the first hard evidence is pressure spiking against the sprays and the PORV. One failed sensor removes the very protection sized for the error it causes.

Immediate actions

StepAction
1Cross-check: pressure + subcooling + charging/letdown totals vs the level reading
2CVCS inventory → MANUAL — stop the auto-charge chasing a phantom low level
3Manage inventory on the diverse evidence (pressure response to heaters/spray is the honest level-proxy)
4Treat the 97 % high-level trip as inoperable — do not lean on it while the channel is failed

Acceptance

No solid-pressurizer event; inventory managed on diverse indications.


PWR-E23 — Reactor Coolant Pump Seal Leak

Failure

rcp_seal_leak — a small containment-side primary leak; severity is the **leak rate as a percentage of make-up capacity** (default 40 %, max 100 %). Unlike every other leak in this chapter, every setting of this slider is inside what charging can replace.

Why this one is different

E06 (SGTR) and E09 (the cold-leg small-break LOCA) are casualties: they outrun make-up, force a trip and drive an EOP. This one does not outrun make-up: charging comes up and holds the inventory. **What it does not hold is containment.** The leak goes to the containment atmosphere, and at power containment pressure climbs until the 3.5 psig safety-injection backup actuates — and **every safety injection trips the reactor** (§3.0 of 09). Measured, full stack, full power, the default 40 %: containment rises about 0.14 psi a minute and SI plus the reactor trip arrive at about 18½ minutes. It is the everyday leak the chemical and volume control system exists to make up — and the one that teaches you to read the board rather than react to it.

It is also not ΔP-modulated. An SGTR stops when you depressurize to steam-generator pressure; this one does not care what the primary is at. You do not terminate it from the control room.

Symptoms

What the board will NOT tell you

PZR LVL LO does not come in. It is 20 points below the programmed level and a held leak parks within a point or two of program, around 52–54 % absolute. If you are waiting for a level alarm to tell you there is a leak, you will wait for the whole shift. Likewise PZR LVL DEV LO (A31) stays clear — the deviation only opens when make-up stops holding, so its silence here is information, not the absence of a problem.

Immediate actions

StepAction
1Confirm the make-up is real: charging high with letdown normal, level at or just below program, subcooling healthy
2Rule out the impostors — letdown isolated or throttled, or a deliberate level-setpoint change, produce the same alarm
3Locate it: containment sump level and humidity, pressurizer relief tank pressure/temperature (a weeping PORV or safety), steam generator activity (a tube leak is E06 territory)
4Trend the charging demand at steady load. Flat = a stable leak you can plan around; rising = it is growing
5Shut down on your own terms before containment reaches 3.5 psig — at the default leak that is under twenty minutes, and SI will trip the reactor if you do not

If it grows past make-up

PZR LVL DEV LO (A31) comes in, charging saturates, and level starts a genuine descent. That is no longer this procedure — go to the loss-of-coolant response and be ready for safety injection at PZR LVL LO LO (12 %).

Acceptance

Leak identified and its size trended, and the shutdown begun deliberately, before containment pressure forces it through a safety injection and reactor trip.

Known model limits, declared: this containment has no structural heat sink, which overstates its pressure rise and makes the 18½ minutes shorter than a real plant's.


4.0 Combined: TMI-class stuck PORV + lying indicator

StepAction
1Inject or encounter stuck_porv_open + porv_indicator_stuck_closed
2Expect: pressure ↓, subcooling ↓, PZR level ↑, PORV light closed
3Isolate block valve; keep HPI
4Full narrative: PWR-X01

5.0 Post-event recovery checklist

#Check
1Reactivity: subcritical / rods in
2Heat sink: SG level held (feed or AFW)
3RCS inventory: stable or improving
4Subcooling: positive and improving
5Pressure: controlled; relief paths isolated if leaking
6Pressurizer heaters: if they were shed by injection or a loss of offsite power, deliberately reloaded or deliberately left shed — not merely forgotten. Pressure control and natural-circulation subcooling both depend on it.
7ESF: intentional AUTO/MAN state
8Failures: cleared or documented still active
9Alarms: understood, not merely silenced

6.0 Related documents

Single-loop note (SGTR): this plant has ONE steam generator, so the classic multi-loop strategy — isolate the faulted SG and steam the intact ones — does not exist here. The EOP is to depressurize the primary to SG pressure, which stops the tube leak (it is driven by the pressure difference), then cool down to RHR. Radiological note: the SG you are steaming through the dump is the contaminated one — in a real plant this is a monitored, minimized release path; multi-loop plants avoid it entirely by steaming their intact generators.

These manuals are licensed CC BY 4.0 — see Legal. Training documents for an educational simulator, not licensing-basis documents for a real plant.