TEST BUILD — an unstable work in progress, not the released simulator. Things here are half-finished on purpose. The stable version is at reactordynamics.com.

PWR Operator Manual · Open the simulator

05 — Mode Transition Procedures

Document: PWR-MT-01
Title: Plant MODE Transitions (Mode 1, At Power through Mode 6, Refueling)
Revision: 24


1.0 Purpose

Define commercial-style plant MODES (Mode 1, At Power … Mode 6, Refueling) for this trainer and provide procedures to move the unit between them — including the full path Mode 5, Cold Shutdown → Mode 1, At Power and Mode 1, At Power → Mode 5, Cold Shutdown.

Also covers turbine load modes (Follow / Manual / Disconnected), AUTO/MAN control, ESF arms, and NIS / trip blocks. Those are not plant MODE numbers.

Related: 04_NORMAL_OPERATIONS.md (N procedures referenced below).


2.0 Plant MODE definitions

These MODES follow the commercial PWR (Westinghouse-style Tech Spec) structure, adapted to SI units and this trainer’s physics.

MODESpoken nameCommercial nameReactivityThermal powerRCS average temperature (class)Trainer support
1Mode 1, At PowerPower OperationCritical (keff ≥ 0.99)> 5 %Hot (≥ ~350 °F / 176.7 °C class)[sim]
2Mode 2, StartupStartupCritical≤ 5 %Hot[sim]
3Mode 3, Hot StandbyHot StandbySubcritical (keff < 0.99)≈ 0Hot (NOP T/P ≈ 546.8 °F / 286 °C no-load, 2235 psi / 15.41 MPa)[sim]
4Mode 4, Hot ShutdownHot ShutdownSubcritical≈ 0Intermediate (between cold and hot)[sim] (transit during heatup/cooldown)
5Mode 5, Cold ShutdownCold ShutdownSubcritical≈ 0Cold (≤ ~200 °F / 93.3 °C class)[sim] — cold_shutdown
6Mode 6, RefuelingRefuelingDeep subcritical≈ 0Cold; vessel head not fully tensionedOut of scope

2.1 Simulator initial-condition mapping

Free Play / engine statePlant MODE
hot_full_powerMode 1, At Power (≈ 100 % — full-power Mode 1)
50_percentMode 1, At Power (partial-power Mode 1)
Critical, power ≤ 5 %Mode 2, Startup
hot_zero_power (Hot Standby)Mode 3, Hot Standby
5_percentMode 1, At Power (low-power ~6 %, just above the 5 % boundary)
hot_shutdownMode 4, Hot Shutdown (250 °F (121.1 °C), 369 psi (2.545 MPa), RHR in service, RCPs secured, both banks in, subcritical)
Post-SCRAM, still hotMode 3, Hot Standby (hot shutdown board; still Mode 3 by temperature class)
Cool / depressurized on RHRMode 4, Hot Shutdown → Mode 5, Cold Shutdown [sim]

2.2 What this trainer can actually step through

Path segmentScope
Mode 3, Hot Standby → Mode 2, Startup → Mode 1, At PowerFully [sim]
Mode 1, At Power → Mode 2, Startup → Mode 3, Hot StandbyFully [sim]
Mode 4, Hot Shutdown → Mode 3, Hot Standby[sim] — start from hot_shutdown, pressurize + start RCPs, heat to NOP on pump heat with the reactor subcritical
Mode 3, Hot Standby → Mode 4, Hot Shutdown → Mode 5, Cold Shutdown[sim] — borate, cool the secondary, depressurize, place RHR, secure RCPs
Mode 6, RefuelingNot modeled

THE COLD END OF THIS PLANT IS MODE 5 AGAIN. The water-property floor moved from 14.5 psi (0.1 MPa) to 0.29 psi (0.002 MPa), so a steam generator at or below Mode 5's 200 °F (93.3 °C) boundary is representable and the Mode 5 ↔ Mode 1 story is driveable end to end on the board, from the cold_shutdown initial condition at 122 °F (50 °C) — or from hot_shutdown (Mode 4) to skip the first leg.

2.3 Turbine load modes (not plant MODES)

Load modeBehavior
FollowElectrical load tracks reactor power (lag ~45 s)
ManualOperator sets MWe
Disconnected0 MWe; SCRAM forces this

Do not say “Mode 1, At Power” for Follow or “Mode 5, Cold Shutdown” for Disconnected.


3.0 Master path — Mode 5, Cold Shutdown to Mode 1, At Power

Procedure ID: PWR-T20
Title: Startup from Mode 5, Cold Shutdown to Mode 1, At Power
Purpose: Take the unit from cold shutdown conditions up to power operation.

Overview

Mode 5, Cold Shutdown          [sim] — cold_shutdown
        │  heatup / pressurize / draw PZR bubble
        ▼
Mode 4, Hot Shutdown           [sim]
        │  continue heatup to NOP
        ▼
Mode 3, Hot Standby           [sim]  ← Free Play starts here
        │  approach to criticality
        ▼
Mode 2, Startup                 [sim]
        │  low-power ops, turbine roll, raise power past 5 %
        ▼
Mode 1, At Power         [sim]
        │  ascend to desired power (e.g. full power)
        ▼
Mode 1, At Power at power (watchstanding)

Phase A — Mode 5, Cold Shutdown → Mode 4, Hot Shutdown → Mode 3, Hot Standby [sim — real rates] → PWR-N01

StepActionMODE after step
A1Plant in Mode 5, Cold Shutdown: subcritical, RCS cold, solid or bubble per commercial practiceMode 5, Cold Shutdown
A2Fill/vent RCS; establish RCP operation when permitted; heat on pump heat, reactor subcriticalMode 5, Cold Shutdown → Mode 4, Hot Shutdown
A3Draw and control pressurizer steam bubble; place heaters/spray in automaticMode 4, Hot Shutdown
A4Heat and pressurize toward normal operating temperature and pressure within commercial heatup limits — and do A5 on the way up, not afterMode 4, Hot Shutdown
A5Re-align the SI accumulators once RCS pressure is above their 665 psi (4.585 MPa) cover gas — they must be aligned before 1000 psi (6.895 MPa) (NUREG-1431 LCO 3.5.1). The cold lineup leaves them isolated; nothing opens them for you. Measured on the real pressurization clock, the window is ~14 plant-minutes wide (cover gas at ~+9 min from the Pressure SP command, 1000 psi at ~+23 min, NOP at ~1.8 plant-hours) — an action inside A4, not a step that follows itMode 4, Hot Shutdown
A6Reach Mode 3, Hot Standby: subcritical, hot, P ≈ 2235 psi (15.41 MPa), Tavg ≈ 546.8 °F (286 °C) (no-load program), heat sink availableMode 3, Hot Standby

Simulator: Phase A is driveable from Mode 5 — load the cold_shutdown initial condition (Mode 5, Cold Shutdown, 122 °F (50 °C); restored 2026-08-31), or hot_shutdown to start at Mode 4 — and perform the heatup: start the RCPs (set_rcp), raise the pressurizer setpoint to draw up to NOP pressure (set_pressure_setpoint), and keep the turbine off line with the dumps shut so the SG bottles, then hand the bottle to the dumps at the top of the ride — set_steam_dump {mode:'auto'}, which with the turbine tripped selects steam-pressure control on the dump setpoint (03 §12.3). That is the whole evolution — heat crossing the tubes has no steam sink on the way up, so it goes into secondary pressure, and the plant rides up on pump heat with the control bank never leaving its cold-shutdown position. Re-measured full stack 2026-08-07 with no rod motion (real rates end to end): ~12.3 plant-hours cold to 567.0 °F (297.2 °C) — the no-load anchor — arriving at ρ = −2828 pcm on 856.8 ppm, control bank still at 0 of 912 steps (the retired engine's bank; the shipped plant is 627 steps — see the note that closes this paragraph). (This paragraph read −3377 pcm on 907 ppm until then, a figure that predates the second moderator re-fit; PWR-N01's own acceptance had the right numbers and this one did not.) It ends less subcritical than the −6287 pcm recorded in older revisions because the old model charged a moderator defect over three times too large on the way up. The thermal ride barely moved across the re-clocks — 545 °F (285.0 °C) arrives at ~11.3 plant-hours and the steady rate is 30.0 °F/hr (16.7 °C/hr) — because pump heat depends on neither the moderator coefficient nor the pressurizer clock. The endpoint reads 567.0 °F rather than the older 548 °F because 567 °F is where the retired engine's Tavg-mode dump program opened and Tavg stopped, and this run was carried to that settling point; it is a measurement-window difference, not a 19 °F physics gain. On the shipped plant that endpoint is a different number and it belongs to a different valve — see the note that closes this paragraph. Or skip Phase A by loading Hot Standby (hot_zero_power) = Mode 3, Hot Standby. (The plant-hour and ρ/ppm figures in this paragraph were measured on the RETIRED engine. On the shipped plant — pwr2 walkthrough replay, 2026-08-31 — the pump-heat class runs ~87–114 °F/hr, arrival is at cold-shutdown boron ~918 ppm / ρ ≈ −3,418 pcm with a 627-step bank, the pressurization is STAGED around the P-11 permissive (complete to 2235 psi only with the secondary hot, or a standing low-steam-pressure SI signal sheds the heaters at the crossing), and the startup walkthrough begins with the dilution 918 → 719 ppm — criticality then sits at 223 of 627 steps (36 % withdrawn), re-measured 2026-09-03. The heat sink at the top of the ride is an operator action, not a given: the cold plant boots with the dump controller out of service, and pressing STEAM DUMP AUTO — which with the turbine tripped selects steam-pressure mode — parks the plant at 547.2 °F (286.2 °C) / 1005 psig with the condenser dumps carrying 0.4–2.9 %. Without it the secondary climbs past the anchor and the atmospheric dump valve relieves at 1042 psig, parking the plant at 551.6 °F (288.7 °C), 4.4 °F (2.4 °C) above the no-load band and venting to atmosphere for the rest of the heatup. Neither figure is the retired engine's 567 °F. The live walkthroughs are the measured authority; see PWR-N01/PWR-T03.)

The approach to criticality is not part of this phase — it is Phase C, and in the campaign it lives in pwr_startup_challenge and pwr_return_to_mode1. Heating a plant to Hot Standby on fission is what the simulator used to do, because the steam generator netted pump heat out of its own steam balance and a pump-heat heatup stalled at 218.69 °F (103.72 °C); that was a modelling fudge and it is gone.

Phase B — Mode 3, Hot Standby lineup [sim] → PWR-N02

StepActionRef
B1Free Play → PWR → Hot Standby (Mode 3, Hot Standby)PWR-T01
B2Complete Mode 3, Hot Standby prerequisites and lineupPWR-N02
B3Confirm subcritical, SR on, control bank in, RCP running, SG availableMode 3, Hot Standby ready

Acceptance: Board is Mode 3, Hot Standby (Hot Standby).

Phase C — Mode 3, Hot Standby → Mode 2, Startup [sim] → PWR-N03

StepActionRef
C0Work the ECC and adjust boron to it — a plant that came up Phase A is at cold-shutdown boron (~857 ppm) and is not ready to start. Measured 2026-09-03, criticality sits at 400 of 627 steps there against 223 at the 719 ppm reference, outside the ±750 pcm acceptance band (111–310 steps)PWR-N02 step 15
C1SR→IR handoff when P-6 met; withdraw Control Bank watching SURPWR-N03
C2Achieve criticality; hold power ≤ 5 %—
C3Declare Mode 2, Startup when critical and power ≤ 5 %Mode 2, Startup

Acceptance: Critical; power ≤ 5 %; SUR controlled → Mode 2, Startup.

Phase D — Mode 2, Startup → Mode 1, At Power [sim] → PWR-N04, N05, N06

StepActionRef
D1Stable low-power ops in Mode 2, StartupPWR-N04
D2Turbine roll / synchronization; begin loadingPWR-N05
D3Raise power above 5 % — plant enters Mode 1, At PowerPWR-N06 / N07
D4Continue ascension to desired Mode 1, At Power power (50 %, 100 %, etc.)PWR-N06
D5Place normal AUTO suite (feed, PZR, optional rods, load Follow)PWR-T10

Acceptance: Critical, power > 5 %, turbine supporting load as intended → Mode 1, At Power.

Phase E — Mode 1, At Power at full power (optional)

StepActionAcceptance
E1Ascend to ~100 % / ~100 MWeFull-power Mode 1, At Power
E2Verify P ≈ 2235 psi (15.41 MPa), SG ~65 %, PZR ~61.5 %, subcooling healthyHFP band

4.0 Master path — Mode 1, At Power to Mode 5, Cold Shutdown

Procedure ID: PWR-T21
Title: Shutdown from Mode 1, At Power to Mode 5, Cold Shutdown
Purpose: Take the unit from power operation down to cold shutdown conditions.

Overview

Mode 1, At Power         [sim]
        │  reduce power / off-load turbine
        ▼
Mode 2, Startup                 [sim]  (optional plateau ≤ 5 %)
        │  SCRAM or full insertion
        ▼
Mode 3, Hot Standby           [sim]
        │  decay heat removal; begin cooldown story
        ▼
Mode 4, Hot Shutdown           [sim]
        │  continue cooldown / depressurize; RHR
        ▼
Mode 5, Cold Shutdown          [sim]  ← genuine cold end state

Phase A — Mode 1, At Power → Mode 2, Startup / Mode 3, Hot Standby [sim]

StepActionRef
A1In Mode 1, At Power, reduce Turbine Load and reactor power in stepsPWR-N08
A2Optional: hold briefly in Mode 2, Startup (critical, ≤ 5 %)—
A3Take turbine to 0 MWe / DisconnectedTurbine-Generator
A4SCRAM (or controlled shutdown then trip)PWR-N14
A5Confirm subcritical, hot, heat sink available → Mode 3, Hot StandbyPWR-T06

Acceptance: Reactor shut down; RCS still hot → Mode 3, Hot Standby.

Phase B — Mode 3, Hot Standby hold [sim]

StepActionAcceptance
B1Maintain SG level (feed or AFW) for decay heatHeat sink held
B2Hold PZR pressure/level; subcooling healthyStable Mode 3, Hot Standby
B3Leave HPI/AFW ESF arms intentionalKnown ESF state

This is the deepest fully simulated shutdown state.

Phase C — Mode 3, Hot Standby → Mode 4, Hot Shutdown → Mode 5, Cold Shutdown [sim, rate-compressed]

StepActionMODE after step
C1Borate to cold-shutdown margin (commercial)Mode 3, Hot Standby
C1aSet the cold lineup before the pressure setpoint moves: HPI/LPI OFF, then — once inside the P-11 permissive — block the low-pressure reactor trip AND the reactor trip on safety injectionMode 3, Hot Standby
C2Cooldown and depressurize within limits using steam dump / AFW / secondaryMode 4, Hot Shutdown
C3Isolate the SI accumulators while descending through 1000 psi (6.895 MPa) — before RCS pressure reaches their 665 psi (4.585 MPa) cover gasMode 4, Hot Shutdown
C4Place RHR in service when pressure permits — you place it; nothing aligns it for you. Throttle the HX split to ~7 % before opening the suction valveMode 4, Hot Shutdown
C5Continue to cold conditions (Tavg ≤ ~199.4 °F (93 °C) class)Mode 5, Cold Shutdown
C6Secure secondary as appropriate; solid plant / cold solid per commercial practiceMode 5, Cold Shutdown

C3 is not optional. The accumulators are passive: nitrogen behind a check valve. Nothing automatic shuts them, and the SI block set at the start of the cooldown blocks pumps, not these tanks. Carry the discharge isolation valve open past 665 psi (4.585 MPa) and all four dump into the RCS — the plant arrives at Mode 5 water-solid, with the accumulators empty and RCS boron dragged up toward the 2500 ppm tank charge. Watch the SIT fill and cover-gas indications on the ECCS side of the board. Isolating at 1000 psig leaves 400 psi (2.76 MPa) of margin. Real plants isolate here too, under administrative control rather than on an automatic signal (NUREG-1431 Rev 4.0 LCO 3.5.1, applicable in *"MODE 3 with RCS pressure

[1000] psig"*; LTOP SR 3.4.12.3 "Verify each accumulator is isolated."). **Re-align them

on the way back up** — Phase A step A5.

Simulator: This is driveable to the Mode 5 end state — the cold plant on RHR — and there is a walkthrough for it: Main Menu → Walkthroughs → Shutdown Part 3, which reproduces N15's performance table. Borate for shutdown margin, block SI before the pressure setpoint moves (the depressurization crosses the 1798 psi (12.4 MPa) SI actuation setpoint; measured with SI armed the pumps inject, the pressurizer goes solid and the plant trips), and block BOTH low-pressure reactor trips — the 1800 psi (12.41 MPa) low-pressure trip and the reactor-trip-on-SI are two separate entries on the same channel, and HPI/LPI OFF blocks neither (measured: the plant scrams in the first cooling leg with either one left armed). Then — with the dumps in steam-pressure mode, which is what AUTO selects on a tripped turbine and the only mode in which the setpoint is read at all (03 §12.3) — lower the steam-dump setpoint (set_steam_dump_setpoint) to cool the secondary and with it the primary — one entry of 120 psi (0.83 MPa); the controller paces the walk at 60 °F/hr (33.3 °C/hr) (03 §12.3, declared departure 2026-09-28), depressurize in step (set_pressure_setpoint, spray) keeping subcooling positive, isolate the accumulators at 1000 psi (6.895 MPa) (discharge valve on the board's ECCS side, close_accumulator_valve), place RHR On below the 425 psig (440 psi / 3.03 MPa) block-open permissive, and secure the RCPs (set_rcp) so RHR draws the RCS to cold. Once RHR carries the cooldown, set its pace with RHR Cooldown Rate (HX flow split) (set_rhr_hx) — walk it up to hold the ~90 °F/h (50 °C/h) cooldown limit rather than opening full-through-the-exchanger on a hot plant. The cold end state matches the cold_shutdown IC. Cooldown rate is time-compressed. PWR-N15 is the companion procedure.


5.0 Individual MODE transition procedures

PWR-T01 — Enter Free Play in Mode 3, Hot Standby

StepAction
1Main Menu → Free Play
2Initial condition Hot Standby
3Confirm Mode 3, Hot Standby: subcritical, hot, SR on, control bank inserted
4Speed 1×; Play; perform PWR-N02

PWR-T02 — Enter Free Play in Mode 1, At Power

StepAction
1Main Menu → Free Play
2Hot Full Power or 50 % Power
3Confirm Mode 1, At Power: critical, power > 5 %, MWe as expected
4Note turbine load mode (default Follow)

PWR-T03 — Mode 3, Hot Standby → Mode 1, At Power (sim path)

StepTransitionProcedure
1Mode 3, Hot Standby → Mode 2, StartupPWR-N03
2Mode 2, Startup low-power holdPWR-N04
3Turbine on linePWR-N05
4Power > 5 % → Mode 1, At PowerPWR-N06
5Desired Mode 1, At Power powerPWR-N07 / N06
6AUTO suitePWR-T10

Abort: Uncontrolled SUR → insert rods; any RPS trip → PWR-T06 (remain/return Mode 3, Hot Standby).

PWR-T04 — Mode 1, At Power → Mode 3, Hot Standby (controlled)

StepActionRef
1Reduce power (still Mode 1, At Power while > 5 %)PWR-N08
2Pass ≤ 5 % critical → Mode 2, Startup (optional hold)—
3Off-load turbine; SCRAMPWR-N14
4Stabilize hot, subcritical → Mode 3, Hot StandbyPWR-T06

PWR-T05 — Mode 1, At Power power increase (stay in Mode 1, At Power)

Raise power within Mode 1, At Power (e.g. 50 % → 100 %). See PWR-N06 / N07. MODE number does not change.

PWR-T06 — Mode 1, At Power (or Two) → Mode 3, Hot Standby by trip

StepAction
1Verify SCRAM — rods in, power falling
2Reset the RPS — the SCRAM control reads PRESS TO RESET. Press it once the rods are seated; it is refused RODS_NOT_INSERTED before that. Resetting re-closes the trip breakers and does not withdraw the rods. Nothing moves the rods until you do this — the open breakers have taken power off the rod drive mechanisms, so WITHDRAW and INSERT are both refused on both banks while the trip is latched (03 §3.5.1)
3Verify turbine Disconnected
4Heat sink: SG level / AFW. Main feedwater isolates on the trip — AFW is the heat sink from here, and in Mode 3 it is sufficient indefinitely. Main feed can be restored at RESTORE on the SG FEED card (03 §9.0) once the RPS is reset, but a stable Hot Standby does not need it
5Inventory / subcooling / HPI as needed
6Declare Mode 3, Hot Standby when subcritical and RCS still hot

Simulator: there is a runnable walkthrough for this — pwr_post_trip, the one you run on the board. Measured full stack from hot_full_power (scram at t = 60 s): the reset is refused at t+1 s with power still at 33 %, and accepted at t+3 s once the rods seat; Mode 3 is reached inside a minute; main feedwater isolates and AFW auto-starts by about t+3 min, holding SG level near 37 % after it falls from 65 %; the plant settles hot and subcritical at 547.2 °F (286.2 °C) and 2235 psi (15.41 MPa). **Step 2 did not exist in this procedure until 2026-08-03** — authoring the walkthrough found it missing, and reset_rps had been reachable on the board since #75 while being named by no procedure, mission or walkthrough at all.

PWR-T20 — Mode 5, Cold Shutdown → Mode 1, At Power

See §3.0 (full master path).

PWR-T21 — Mode 1, At Power → Mode 5, Cold Shutdown

See §4.0 (full master path).

PWR-T22 — Mode 2, Startup → Mode 3, Hot Standby (reject startup)

StepAction
1From Mode 2, Startup, insert rods or SCRAM
2Confirm subcritical
3Hold hot → Mode 3, Hot Standby

PWR-T23 — Mode 3, Hot Standby → Mode 2, Startup only (criticality practice)

StepAction
1PWR-N02 then PWR-N03
2Hold power ≤ 5 %
3Do not enter Mode 1, At Power until ready

6.0 Turbine load mode transitions (at Mode 1, At Power)

These change grid/turbine state, not plant MODE (you remain Mode 1, At Power if still critical > 5 %).

PWR-T07 — Follow → Manual

  1. Select Manual on Turbine-Generator.
  2. Set MWe near current output, then ramp slowly.
  3. Match reactor power; keep feed AUTO.

CAUTION: Large step cuts can trip the plant back toward Mode 3, Hot Standby.

PWR-T08 — Manual → Follow

  1. Stabilize power.
  2. Select Follow.
  3. Confirm load tracks reactor power.

PWR-T09 — → Disconnected

  1. Prefer power reduction first if controlled.
  2. Disconnect / turbine trip / or SCRAM.
  3. If SCRAM: plant → Mode 3, Hot Standby; load Disconnected.

7.0 Control and ESF mode transitions

PWR-T10 — Normal AUTO suite in Mode 1, At Power

ChannelState
Feed → SG levelAUTO
PZR pressureAUTO
CVCS make-upAUTO
TurbineFollow or Manual per dispatch
Rods → TavgAUTO optional (capture T-ref carefully)
Steam dumpAUTO — Tavg mode here, because the turbine is on line (03 §12.3)
HPI / AFW ESFAUTO unless testing

PWR-T11 — Single channel AUTO → MANUAL

Operate underlying control or select MAN; re-engage AUTO when stable.

PWR-T12 — ESF MANUAL → re-arm AUTO

Press AUTO on Emergency card after manual intervention. Standing start conditions may fire immediately.

PWR-T13 — SR → IR handoff (Mode 3, Hot Standby / Mode 2, Startup startup)

IR ≥ 1e-10 A (P-6) → confirm INTER RANGE is reading, then block SR HIGH FLUX on the Trip Blocks panel: it blocks the source-range trip and switches the detector off, and the intermediate range becomes the instrument to read. Miss it and the source range trips the reactor at 1e5 cps. On the way down the block clears itself below 5e-11 A and the detector comes back on.

PWR-T14 — Startup trip blocks (entering Mode 1, At Power)

Above P-10 (8 %) — already Mode 1, At Power — block IR high (25 %) first, then PR low setpoint (35 %). Two separate presses; the IR one also clears the 20 % rod stop. Both auto-reinstate below P-10.

Take them with power comfortably above 10 %, not at 8 %. The permissive is graded on the indicated power-range channel, which carries about ± 0.3 % with no 2-of-4 coincidence behind it, so a block taken just over 8 % is revoked within seconds: measured, one press survives 1 s at 8.19 % power, 4 s at 8.72 %, 105 s at 9.10 %, and indefinitely from 9.36 %. Below the permissive the BLOCK control does not accept the press at all; above it the press is always accepted and it is the block that does not hold.

PWR-T15 — Learning ↔ Realistic display

Training display only; does not change plant MODE.


8.0 Transition map

 Mode 6, Refueling     OUT OF SCOPE
        │
 Mode 5, Cold Shutdown ──────── [sim] heatup ─────────┐
        ▲                                                 │
        │ [sim] cooldown                                  ▼
 Mode 4, Hot Shutdown ◄─────────────────────── Mode 3, Hot Standby  [sim]
        ▲                                                 │
        │                                                 │ N02 [sim]
        │                                                 ▼
        │                                          Mode 2, Startup  [sim]
        │                                                 │
        │ N14 / trip                                      │ N04–N06 [sim]
        │                                                 ▼
        └─────────────── Mode 1, At Power  [sim] ── full power

Operator goal paths:

GoalProcedure
Cold to powerPWR-T20 Mode 5, Cold Shutdown → Mode 1, At Power
Power to coldPWR-T21 Mode 1, At Power → Mode 5, Cold Shutdown
Hot standby to power (sim-only)PWR-T03 Mode 3, Hot Standby → Mode 1, At Power
Power to hot standby (sim-only)PWR-T04 Mode 1, At Power → Mode 3, Hot Standby

9.0 Related documents

These manuals are licensed CC BY 4.0 — see Legal. Training documents for an educational simulator, not licensing-basis documents for a real plant.